Flame Resistance |
|||
|
Level
|
USA
|
CSA*
|
Europe*
|
|
FR-00
|
Little or no flame retardancy, cable ignites and burns easily, and will not extinguish itself |
---
|
---
|
|
FR-01
|
UL 62, Horizontal Flame test one 30 second flame application, must not emit flame or glowing particles | FT2, one 30 second flame application, must not emit flame or glowing particles | VDE 0472 Part 804 one 1-minute flame application, must not ignite or emit flames |
|
FR-02
|
UL VW-1, Vertical Flame test, five 15-second flame applications, must not emit flame or glowing particles | FT1, Vertical flame test, five 15 second flame applications, must not emit flame or glowing particles | IEC 60332-1, flame application time varies by cable diameter, must self-extinguish |
|
FR-03
|
UL Vertical Tray test exposed to flame for twenty minutes, damage cannot exceed 8 feet | FT4, Vertical Tray test exposed to flame for twenty minutes, damage cannot exceed 5 feet | IEC 60332-3-24, exposed to flame for twenty minutes, damage cannot exceed 8.2 feet |
|
FR-03.1
|
UL Vertical Tray Fire Propagation exposed to flame for twenty minutes, damage cannot exceed 8 feet, smoke release not to exceed 95m2 | FT4-ST1,Vertical Tray Fire Propagation exposed to flame for twenty minutes, damage cannot exceed 8 feet, smoke release not to exceed 95m2 | IEC 60332-3-25, exposed to flame for 20 minutes damage, cannot exceed 8.2 feet. |
|
FR-04
|
UL Flame test for Riser cables Flame spread cannot exceed 12 ft.; Measured temperature at any point cannot be greater than 850°F |
----
|
----
|
|
FR-05
|
UL Flame test for Plenum cables exposed to flame for twenty minutes, damage cannot exceed 5 feet, peak smoke optical density not to exceed .50 | FT6, exposed to flame for twenty minutes, damage cannot exceed 5 feet peak smoke optical density not to exceed .50 | IEC 61034-2 exposed to flame for a maximum of 40 minutes, minimum value of 60% light transmittance. |
|
*Note: These flame standards are mentioned for purposes of reference only. Some Canadian and European test standards are not necessarily represented here as complete equivalents to the US Standards but have been referenced due to some similarities in requirements. Refer to the individual standards for detailed test procedures and any comparability evaluations. Lapp cables are manufactured to comply with varying degrees of flame resistance requirements. Depending upon your application, certain levels of flame resistance are necessary in order to meet specific end use requirements. Flammability ratings generally determine the end use application, which is generally dictated by local or national electrical codes. Certain applications require a minimal amount of flame resistance such as UL 62 or CSA FT2 for flexible cordage. In this instance, the end use of these products do not deem the necessity of imposing a high flammability requirement. Other applications such as cables that will be installed permanently within an industrial building, commercial dwelling or family residence will most likely require a higher degree of flammability resistance such as a UL Vertical Tray or CSA FT4. Whatever the end use application, the Lapp Group offers a wide variety of cable products meeting different levels of flame resistance that will meet your requirements. |
|||
|
||